Product
Function: | current, leakage current, transformation ratio, higher harmonic current, phase, electric power, power, power factor of the High and low voltage lines |
Jaw size: | φ50mm |
Range: | AC0.0mA~1200A |
Accuracy: | ±1.0% |
Turn Ratio: | 4000:1 (can be customized) |
Lines Voltage: | AC ≤60kV |
Function |
current, leakage current, transformation ratio, higher harmonic current, phase, electric power, power, power factor of the High and low voltage lines |
Features | CT clamp structure |
output Method | Current sensing output |
Jaw Size | Φ50mm |
Secondary Development Display Window | 46*30mm |
Range | AC 0.0mA~1200A Resolution: AC 0.1mA Accuracy: ±1.0%FS(50Hz/60Hz; 23 °C±2 °C) The wire is in the center of the jaw |
Phase Error | ≤3°(50Hz/60Hz;23 °C±2°C) |
Turn Ratio | 4000:1 (can be customized) |
Reference Load | RL: 0~10A≤50Ω; 0~100A≤5Ω; 0~1200A≤0.5Ω |
Weight | 300g |
Dimensions | L/T/H 87mmX 37mmx 262mm |
Output Interface | 10cm long, can be connected by opening the upper and lower covers |
Electric field Interference | about 10mA when the external electric field 100A approaches 30mm |
Current Frequency | 45Hz~65Hz (measured current frequency) |
Line Voltage | AC60kV and below, circuit test telescopic insulation poles should be fully opened |
Working Temperature | -25°C~55 °C |
Medium Strength | AC3700V/rms (between iron core and shell) |
Current Frequency | 45Hz~65Hz(measured current frequency) |