Product
| Function: | current, leakage current, transformation ratio, higher harmonic current, phase, electric power, power, power factor of the High and low voltage lines |
| Jaw size: | φ50mm |
| Range: | AC0.0mA~1200A |
| Accuracy: | ±1.0% |
| Turn Ratio: | 4000:1 (can be customized) |
| Lines Voltage: | AC ≤60kV |

| Function |
current, leakage current, transformation ratio, higher harmonic current, phase, electric power, power, power factor of the High and low voltage lines |
| Features | CT clamp structure |
| output Method | Current sensing output |
| Jaw Size | Φ50mm |
| Secondary Development Display Window | 46*30mm |
| Range | AC 0.0mA~1200A Resolution: AC 0.1mA Accuracy: ±1.0%FS(50Hz/60Hz; 23 °C±2 °C) The wire is in the center of the jaw |
| Phase Error | ≤3°(50Hz/60Hz;23 °C±2°C) |
| Turn Ratio | 4000:1 (can be customized) |
| Reference Load | RL: 0~10A≤50Ω; 0~100A≤5Ω; 0~1200A≤0.5Ω |
| Weight | 300g |
| Dimensions | L/T/H 87mmX 37mmx 262mm |
| Output Interface | 10cm long, can be connected by opening the upper and lower covers |
| Electric field Interference | about 10mA when the external electric field 100A approaches 30mm |
| Current Frequency | 45Hz~65Hz (measured current frequency) |
| Line Voltage | AC60kV and below, circuit test telescopic insulation poles should be fully opened |
| Working Temperature | -25°C~55 °C |
| Medium Strength | AC3700V/rms (between iron core and shell) |
| Current Frequency | 45Hz~65Hz(measured current frequency) |